Uptime Business Products banner.  Liebert UPS
 
Liebert UPStation GXT UPS Liebert UPStation GXT Features:
  • True On-Line design provides 100% effectiveness plus there's another important benefit
  • Provides for wide input voltage correction
  • Available in sizes from 700 - 10,000 VA
  • Rack-mount or tower versions available
  • Sophisticated SNMP and load management capability
  • Hot-swappable batteries
  • Many battery reserve time options available
  • Warranted for 2 years, the strongest warranty in the industry 
  • Backed by Liebert, a name you can trust
UPStation
GXT
the 100%
Solution
Liebert UPStation GXT UPS
Liebert UPStation Liebert UPStation GXT UPS
Liebert UPStation GXT UPS Liebert GXT UPS

On-Line design means that the Liebert GXT corrects for frequency deviations in the input power.  Power quality experts tell us that the power grid in the United States and most of Western Europe does not experience frequency deviations.  These grids are rock solid 60 Hz (50 Hz for Europe).

So why is protection from input frequency changes important?  Good question!  Allow us to answer:

  • Many corporations have locations in developing countries where the power grid is not frequency stable.
  • Even in frequency stable areas, emergency diesel generators are often as frequency unstable as the grids in developing countries.

OK, so the Liebert GXT corrects for frequency, what do the other off-line or line interactive systems do when frequency varies?

Another good question!  These systems either:

  1. Pass the out-of-specification power on to your sensitive computer equipment (is this why you buy a UPS?) ....or..
  2. Go to battery power... Good, right??  Well suppose the frequency deviation lasts for a longer time than your batteries...  You have input power (outside of the frequency tolerance) but.... Your server is down!!!  

This means that with the Liebert UPStation GXT, you can develop a uniform UPS performance specification which includes the special needs for international installations, plus will assure trouble-free operation on emergency diesel power now or in the future!

We've told you what the competition does (really doesn't do).  What exactly does the Liebert GXT do?

The Liebert UPStation corrects for the following input power problems WITHOUT USING THE BATTERY:

  • Frequency 57.6 - 62.4 Hz (for 60 Hz grids) or 48.1 - 51.9 Hz (for 50 Hz grids)
  • Input voltage 83 - 134 volts (for 120 volt systems)

This all means that the GXT corrects power when it's available, preserving valuable battery energy for critical power outages.

 

Liebert GXT UPS Specifications

Part Number Rating (VA/W) Type Voltage Backup Time (FL/HL) Listing
GXT700MT-120 700/490 Mini-Tower 120 VAC 5min/16min UL / c-UL
GXT700MT-230 700/490 Mini-Tower 230 VAC 6min/18min TUV / CE
GXT1000MT-120 1000/700 Mini-Tower 120 VAC 7min/19min UL / c-UL
GXT1000MT-230 1000/700 Mini-Tower 230 VAC 6min/18min TUV / CE
GXT1000RT-120 1000/700 Rack/Tower (1) 120 VAC 7min/19min UL / c-UL
GXT1000RTE-120 1000/700 Rack/Tower (1) 120 VAC 18min/50min UL / c-UL
GXT1000RT-230 1000/700 Rack/Tower (1) 230 VAC 6min/18min TUV / CE
GXT1000RTE-230 1000/700 Rack/Tower (1) 230 VAC 17min/49min TUV / CE
GXT1500RT-120 1500/1050 Rack/Tower (1) 120 VAC 5min/15min UL / c-UL
GXT1500RTE-120 1500/1050 Rack/Tower (1) 120 VAC 15min/----- UL / c-UL
GXT1500RT-230 1500/1050 Rack/Tower (1) 230 VAC 5min/15min TUV / CE
GXT1800RT-208 1800/1260 Rack/Tower (1) 208 VAC 11min/27min UL / c-UL
GXT2000RT-120 2000/1400 Rack/Tower (1) 120 VAC 11min/27min UL / c-UL
GXT2000RT-230 2000/1400 Rack/Tower (1) 230 VAC 11min/27min TUV / CE
GXT2700RT-208 2700/1890 Rack/Tower (1) 208 VAC 6min/15min UL / c-UL
GXT3000RT-120 3000/2100 Rack/Tower (1) 120 VAC 6min/15min UL / c-UL
GXT3000RT-230 3000/2100 Rack/Tower (1) 230 VAC 6min/15min TUV / CE
Note 1.  To mount as a rack unit a side rail kit (#RS400) is necessary.